How the calculation works

Each device row adds its power at the switch port (the PSE, power sourcing equipment):

  • Class maximum (the default): the most a port can supply for that class under IEEE 802.3.
  • Watts at the device (optional): the data sheet maximum for the device (the PD, powered device) plus the class’s worst-case cable loss, the difference between the PSE and PD figures in the table below.
Class At the switch (PSE) At the device (PD) Switch type needed
0 15.4 W 12.95 W PoE (802.3af)
1 4 W 3.84 W PoE (802.3af)
2 7 W 6.49 W PoE (802.3af)
3 15.4 W 12.95 W PoE (802.3af)
4 30 W 25.5 W PoE+ (802.3at)
5 45 W 40 W PoE++ (802.3bt Type 3)
6 60 W 51 W PoE++ (802.3bt Type 3)
7 75 W 62 W PoE++ (802.3bt Type 4)
8 90 W 71.3 W PoE++ (802.3bt Type 4)

Class power from IEEE 802.3 as tabulated in Power over Ethernet (Wikipedia, read October 2026). The figures at the device assume the standard’s worst case of 100 meters of cable; shorter runs lose less.

Then:

  • Usable budget = switch PoE budget × (1 − reserve %)
  • Total draw = the sum of quantity × watts at the switch, for every device the switch type can power
  • Headroom = usable budget − total draw
  • Ports used = every device, including any powered by an injector
  • More that fit, per row = the smaller of headroom ÷ that device’s watts (rounded down) and the free ports

A device whose class is above the switch type is left out of the switch’s total and flagged for a midspan injector or a switch of a higher type. The device type only suggests a starting class (class 2 for phones, 4 for access points, 3 for cameras, access control and other devices): these are planning assumptions, so set each row’s class from the data sheet.

Worked example

A 48-port PoE+ switch with a 740 W PoE budget, powering 30 IP phones at class 2, 6 access points at class 4, 8 cameras at class 3 and 2 door controllers at class 3:

Devices Each at the switch Total
30 IP phones, class 2 7 W 210 W
6 access points, class 4 30 W 180 W
8 cameras, class 3 15.4 W 123.2 W
2 access control devices, class 3 15.4 W 30.8 W
Total 544 W

The switch uses 544 W of 740 W (73.5%), leaving 196 W of headroom. The devices take 46 of 48 ports, so only 2 more access points fit, even though the power would cover 6 (196 ÷ 30 = 6.5): this switch runs out of ports before power.

Swap the access points for a model that needs class 6 and each needs 60 W per port, more than PoE+ supplies. They would need injectors or an 802.3bt switch.

Before you buy

  • Check the switch’s PoE budget for the power supply you actually have. Many switches list a higher budget only with a second or larger supply.
  • Plan the switch’s own uplinks: they aren’t PoE ports and aren’t counted here.
  • PoE devices go down with the switch. Put PoE switches for phones, cameras and door controllers on a UPS; the UPS runtime calculator sizes one from the switch’s input power, which is the PoE draw plus the switch itself, divided by the power supply’s efficiency.