How the calculation works
Apparent power in kVA is volts × amps, with √3 for three-phase:
- Single-phase: kVA = volts × amps ÷ 1,000
- Three-phase: kVA = √3 × volts × amps per phase ÷ 1,000, with the line-to-line voltage and √3 ≈ 1.732
No power factor is involved. The answer is the capacity of the conductors or breaker in the same unit that UPS, generator and transformer nameplates use, so you can compare them directly. To find the real power in kW, multiply by the load’s power factor.
The default is 480 V three-phase, a common voltage for building services and datacenter feeders in North America. Change it for a 208 V or 415 V feed, or a single-phase supply.
A 480 V feeder’s two voltages. A service or feeder labeled 277/480 V or 480Y/277 V has 480 V between phases (line-to-line) and 277 V from each phase to neutral (480 ÷ √3, line-to-neutral). The amps on the breaker or feeder are per phase. Enter 480 V with three-phase selected; entering 277 V would understate the kVA by a factor of √3.
Worked example
A building has a 200 A, 480 V three-phase service available for a server room:
- kVA = 1.732 × 480 × 200 ÷ 1,000 = 166.28 kVA (166,277 VA)
That is the full rating. The usable figure for a continuous load is lower; in North America, continuous loads are commonly planned at 80% of the breaker rating.
A 100 A, 208 V three-phase panel in an existing IT room:
- kVA = 1.732 × 208 × 100 ÷ 1,000 = 36.03 kVA