How the calculation works

The current at a given apparent power depends only on the voltage and the circuit type:

  • Single-phase: amps = kVA × 1,000 ÷ volts
  • Three-phase: amps per phase = kVA × 1,000 ÷ (√3 × volts), with the line-to-line voltage and √3 ≈ 1.732

Entering the nameplate kVA gives the full-load current (often abbreviated FLA on nameplates), the current per phase when the unit runs at its rating. No power factor is needed: kVA is volts × amps, so it does not depend on one. If you start from a load in kW, convert it to kVA first.

The default is 480 V three-phase, a common output voltage for generators, large UPS systems and the primary side of datacenter transformers in North America. Change it for 208 V, 400 V or 415 V equipment, or for single-phase units.

480Y/277 V nameplates. A transformer secondary or generator labeled 480Y/277 V has 480 V between any two phases (line-to-line) and 277 V from each phase to neutral (480 ÷ √3, line-to-neutral). The 277 V is commonly used for lighting circuits. For full-load current, enter 480 V with three-phase selected.

Worked example

A 500 kVA standby generator with a 480 V three-phase output:

  • amps per phase = 500,000 ÷ (1.732 × 480) = 500,000 ÷ 831.4 = 601.41 A

The same 500 kVA at 208 V three-phase:

  • amps per phase = 500,000 ÷ (1.732 × 208) = 1,387.86 A

More than twice the current for the same kVA, which means larger conductors and switchgear at the lower voltage.