How the calculation works

Real power in watts comes from the current, the voltage, the circuit type and the power factor (PF):

  • Single-phase: watts = volts × amps × PF
  • Three-phase: watts = √3 × volts × amps × PF, where amps is the current on one phase, volts is the line-to-line voltage and √3 ≈ 1.732

Volts × amps on its own (× √3 on three-phase) is the apparent power in volt-amperes (VA). The calculator shows both: watts are what the equipment uses, VA is what the circuit carries. The power factor links them, and the default of 1.0 makes the two equal. IT equipment with power-factor-corrected supplies runs close to 1.0 under load; if your PDU or meter reports a power factor, enter it.

The default is a 208 V single-phase circuit, a common feed for a single server or a small PDU in North American datacenters.

Which voltage is your reading on? In a 208Y/120 V panel, a branch circuit wired from one phase to neutral runs at 120 V, and one wired between two phases runs at 208 V. A clamp meter shows the same kind of amps on both, so the voltage you enter decides the answer: 10 A is 1,200 W on the 120 V branch and 2,080 W on the 208 V one (PF 1.0). Use three-phase only when the reading comes from a three-phase feed, and then enter the line-to-line voltage (208 V here, not the 120 V line-to-neutral voltage, which is 208 ÷ √3).

Worked example

A server PDU input on a 208 V single-phase circuit reads 16 A, and its display shows a power factor of 0.95:

  • watts = 208 × 16 × 0.95 = 3,161.6 W
  • apparent power = 208 × 16 = 3,328 VA

A 120 V branch circuit feeding a network switch and a console server reads 12 A. At a power factor of 1.0:

  • watts = 120 × 12 = 1,440 W, which is exactly 80% of a 15 A, 120 V circuit, the usual planning limit for a continuous load

A small three-phase PDU on a 208 V feed reads 10 A per phase. At a power factor of 1.0:

  • watts = 1.732 × 208 × 10 = 3,602.7 W