How the calculation works

Each row is one device type: a device from the list, its height in rack units (U), the quantity, watts per device and weight per device.

  • RU used = Σ height × quantity. Free = cabinet height (42, 45 or 48 U) − RU used. When the devices need more space than the cabinet has, the result says how many U it is over.
  • Power = Σ watts × quantity, in W and kW.
  • Weight = Σ weight × quantity, in the unit you choose, with the other unit alongside (1 lb = 0.45359237 kg).
  • Against the load ratings = weight ÷ the static or dynamic rating you enter, with the weight to spare or the amount over.
  • Front elevation: devices fill the cabinet from U1 at the bottom upward, in row order, one after another. A device that doesn’t fit in the space left is listed as not fitting, and smaller devices after it still fill the remaining space. Zero-U devices (height 0) count for power and weight but are not drawn.

One rack unit is 1.75 inches (44.45 mm); see rack unit. Heights are whole units. The watts are the figures you enter, so the total is only as good as they are: measured draw is better than nameplate ratings.

Worked example

A 42U cabinet with a static load rating of 2,000 lb and a dynamic rating of 1,500 lb:

RowDeviceHeightQtyWatts eachWeight eachTakes
1Storage2 U2650 W60 lbU1–U4
2Server2 U8550 W45 lbU5–U20
3Server1 U6350 W30 lbU21–U26
4Firewall1 U2150 W15 lbU27–U28
5Switch1 U2250 W18 lbU29–U30
6Patch panel1 U20 W3 lbU31–U32
7PDU0 U20 W15 lbside channels
  • Rack units: 4 + 16 + 6 + 2 + 2 + 2 = 32 U used, 10 U free.
  • Power: 1,300 + 4,400 + 2,100 + 300 + 500 = 8,600 W (8.6 kW).
  • Weight: 120 + 360 + 180 + 30 + 36 + 6 + 30 = 762 lb (345.6 kg).
  • Static rating: 762 ÷ 2,000 = 38.1%, with 1,238 lb to spare. Dynamic rating: 762 ÷ 1,500 = 50.8%.

At 8.6 kW, the colocation power calculator shows which circuits carry the load, and the server room cooling calculator converts the same watts into the cooling it needs.