How the calculation works
Each row is one device type: a device from the list, its height in rack units (U), the quantity, watts per device and weight per device.
- RU used = Σ height × quantity. Free = cabinet height (42, 45 or 48 U) − RU used. When the devices need more space than the cabinet has, the result says how many U it is over.
- Power = Σ watts × quantity, in W and kW.
- Weight = Σ weight × quantity, in the unit you choose, with the other unit alongside (1 lb = 0.45359237 kg).
- Against the load ratings = weight ÷ the static or dynamic rating you enter, with the weight to spare or the amount over.
- Front elevation: devices fill the cabinet from U1 at the bottom upward, in row order, one after another. A device that doesn’t fit in the space left is listed as not fitting, and smaller devices after it still fill the remaining space. Zero-U devices (height 0) count for power and weight but are not drawn.
One rack unit is 1.75 inches (44.45 mm); see rack unit. Heights are whole units. The watts are the figures you enter, so the total is only as good as they are: measured draw is better than nameplate ratings.
Worked example
A 42U cabinet with a static load rating of 2,000 lb and a dynamic rating of 1,500 lb:
| Row | Device | Height | Qty | Watts each | Weight each | Takes |
|---|---|---|---|---|---|---|
| 1 | Storage | 2 U | 2 | 650 W | 60 lb | U1–U4 |
| 2 | Server | 2 U | 8 | 550 W | 45 lb | U5–U20 |
| 3 | Server | 1 U | 6 | 350 W | 30 lb | U21–U26 |
| 4 | Firewall | 1 U | 2 | 150 W | 15 lb | U27–U28 |
| 5 | Switch | 1 U | 2 | 250 W | 18 lb | U29–U30 |
| 6 | Patch panel | 1 U | 2 | 0 W | 3 lb | U31–U32 |
| 7 | PDU | 0 U | 2 | 0 W | 15 lb | side channels |
- Rack units: 4 + 16 + 6 + 2 + 2 + 2 = 32 U used, 10 U free.
- Power: 1,300 + 4,400 + 2,100 + 300 + 500 = 8,600 W (8.6 kW).
- Weight: 120 + 360 + 180 + 30 + 36 + 6 + 30 = 762 lb (345.6 kg).
- Static rating: 762 ÷ 2,000 = 38.1%, with 1,238 lb to spare. Dynamic rating: 762 ÷ 1,500 = 50.8%.
At 8.6 kW, the colocation power calculator shows which circuits carry the load, and the server room cooling calculator converts the same watts into the cooling it needs.