How the calculation works

Heat output follows directly from the electrical power drawn:

  • BTU/hr = watts × 3.41214
  • tons of cooling = BTU/hr ÷ 12,000

One watt is 3.412142 BTU/hr (International Table BTU, per NIST Special Publication 811). The calculator uses 3.41214; most references round to 3.412, which changes results by less than 0.01%. One ton of refrigeration is defined as 12,000 BTU/hr.

The calculator assumes all the electrical power the equipment draws becomes heat in the room, which holds for servers, storage and network gear. For a realistic heat load, enter measured or typical draw rather than power supply ratings, which are maximums.

This converts one figure. Sizing cooling for a whole room also adds lighting, people, heat through walls and windows, and a design margin, and the cooling equipment’s own capacity depends on the conditions it runs in.

Worked example

A colocation cabinet draws 10,000 W (10 kW):

  • BTU/hr = 10,000 × 3.41214 = 34,121 BTU/hr
  • tons = 34,121 ÷ 12,000 = 2.84 tons

With the rounded factor 3.412 the heat output is 34,120 BTU/hr, 1.4 BTU/hr less.

A single 500 W server:

  • BTU/hr = 500 × 3.41214 = 1,706 BTU/hr
  • tons = 1,706 ÷ 12,000 = 0.142 tons