How the calculation works

  • Facility load = IT load (kW) × PUE.
  • IT energy = IT load × hours, in kWh. Facility energy = IT energy × PUE.
  • Overhead energy = facility energy − IT energy: cooling, power conversion losses and lighting.
  • Emissions = facility energy × emission factor, in kg; ÷ 1,000 for metric tons (t). The overhead’s share uses the same factor.
  • Energy cost (optional) = facility energy × the rate per kWh.

The emission factor can be entered in kg/kWh, g/kWh or lb/MWh. The calculator converts it to kg/kWh: g/kWh ÷ 1,000, and lb/MWh × 0.45359237 ÷ 1,000 (one pound is exactly 0.45359237 kg). Hours default to 8,760, a 365-day year; use 8,784 for a leap year. The PUE calculator uses 8,766 hours, the average year, so its annual cost differs slightly from this calculator’s at the default.

Assumptions: the IT load and PUE are averages over the period, the factor applies to all the energy, and all of the facility’s energy is attributed to this load. The result is CO₂e if your factor is CO₂e, or CO₂ if it covers CO₂ only. No grid averages are built in: every number is yours.

Worked example

A 250 kW average IT load in a facility with a PUE of 1.5, on a grid with a factor of 0.4 kg CO₂e/kWh (881.8 lb/MWh), at $0.12/kWh, over a 365-day year:

  • Facility load: 250 × 1.5 = 375 kW.
  • IT energy: 250 × 8,760 = 2,190,000 kWh. Facility energy: × 1.5 = 3,285,000 kWh (3,285 MWh).
  • Overhead energy: 3,285,000 − 2,190,000 = 1,095,000 kWh.
  • Emissions: 3,285,000 × 0.4 = 1,314,000 kg = 1,314 t CO₂e, of which 438 t come from the overhead.
  • Per kW of IT: 1,314 ÷ 250 = 5.26 t a year.
  • Energy cost: 3,285,000 × $0.12 = $394,200 a year.

At the same IT load, lowering the PUE to 1.3 removes 0.2 × 2,190,000 = 438,000 kWh a year, which is 175.2 t CO₂e at this factor.